Heat-pump noise in 2026: choosing the assessment route and data

ACP Insights & Guidance

A heat pump noise assessment needs the right planning route, equipment data and installation layout. Identify the relevant operating scenarios, including night-time use, before the design or calculation is fixed.

The practical answer

Confirm the jurisdiction and planning route first. Then agree the sound-power data, receiver positions and overnight operation with the responsible assessor. A quiet-mode brochure value, a boundary measurement and a method’s receiver criterion are not interchangeable.

Choose the heat-pump noise assessment route before commissioning work

A heat pump noise brief should start with the installation and its planning route. The 2026 professional advice note from the Institute of Acoustics (IOA) and Chartered Institute of Environmental Health (CIEH) sets out proportionate options for domestic installations where permitted development rights do not apply.

Start by checking the planning position for the relevant UK nation and site. An acoustic calculation alone does not establish permitted development rights. Also distinguish a domestic installation from a commercial or more complex plant proposal.

The following route prompts help you prepare a discussion with the installer, planning adviser and acoustician. They do not determine permission or provide a noise calculation.

Heat pump noise: three routes in the 2026 note

Route prompts for domestic proposals outside permitted development
Starting pointRoute to discuss
Permitted development is unavailable for a non-acoustic reasonPDR+: installer-led MCS 020a calculation, where no greater caution is needed.
PDR+ indicates a minor exceedanceLevel 1: a suitably qualified acoustician considers sound propagation and the note’s 37 dB(A) criterion.
Exceptional or sensitive circumstancesLevel 2: a suitably qualified acoustician assesses the detailed context, including relevant cumulative effects.

For Level 1, the note uses 37 dB(A) incident sound pressure level, assessed one metre from the centre of a habitable-room window or door. Exclude the reflection from that assessment façade. It is not a universal boundary limit or the manufacturer’s sound power rating. Confirm the method and local requirements with the responsible assessor.

For help selecting a project scope, see ACP’s heat-pump noise assessment service.

Heat-pump noise at night: define the operating scenarios

Heat-pump noise at night needs a clear account of what the system will actually do. Ask the installer to identify heating, hot-water and other relevant operating scenarios, including any controls that change operation overnight. Then ask the acoustician which scenarios and assessment periods the chosen method requires.

Do not assume that a quiet-mode setting is an acceptable assessment input. MCS 020 a) Issue 1.1 explicitly excludes low-noise-mode sound power from its specified calculation input. Other routes have their own data requirements, so record the method before choosing a supplier value.

Source

Exact model, sound power and the conditions behind the data.

Operation

Relevant overnight scenarios and the controls that govern them.

Receiver

Nearby rooms, assessment positions and the actual installation geometry.

Keep sound power and sound pressure separate

Sound power describes a source’s acoustic emission under stated conditions. Sound pressure describes the sound at a receiving position and depends on distance, surroundings and other factors. Therefore, a product’s sound power value cannot be compared directly with a receiver sound-pressure criterion.

Similarly, a quoted ‘noise level at one metre’ needs its test conditions and acoustic quantity. Ask the manufacturer to clarify ambiguous data. Preserve the original sheet so the assessor can check exactly what the figure represents.

Check controls, capacity and commissioning together

If a proposed control restricts operation overnight, the heating designer should confirm its effect on comfort, hot water and system performance. The acoustician should then review the same operating assumption. A measure is not robust if normal use routinely overrides it.

Also coordinate mounting, pipework, airflow and maintenance access. Screens and enclosures need both acoustic and mechanical review. After installation, check the equipment identity, position and control settings against the agreed brief, and refer material substitutions back to the responsible designers.

Illustrative change-control example

An installer proposes moving a unit beside a different neighbouring bedroom window. The product is unchanged, but the distance and reflecting surfaces differ. The team therefore returns the revised layout to the assessor before relying on the previous result.

The outcome may be a revised calculation, a design adjustment or a different assessment scope. The example does not predict a noise level or imply that a particular position will comply.

Prepare the heat pump noise data request

Send the exact proposed model and its supporting data, not a sales description for a product range. Also keep the original data sheet with its date and version. Then ask the supplier to identify the operating conditions behind each value.

Information to request before the acoustic brief is fixed
RecordPractical request
Equipment identityManufacturer, complete model reference, number of units and relevant accessories.
Sound dataSound power information, its test conditions and available maximum operating data. Label any quiet-mode value clearly; do not use it as a substitute for the route’s specified data.
Design operationHeating and hot-water assumptions, relevant cooling operation and how controls will operate.
LocationA scaled layout, elevations, mounting position, distances, nearby windows and proposed screens.
Installation constraintsManufacturer clearances, airflow needs, maintenance access, mounting and pipework arrangements.
Decision recordWho supplied each item, who accepted it for assessment and what still needs confirmation.

In addition, the note distinguishes the data used for different routes. For Level 1 it calls for maximum sound power where available, otherwise a 5 dB adjustment to the energy-label value. Therefore, let the acoustician select and justify the input. Do not substitute a quieter marketing figure.

Resolve the location while options remain

Discuss siting before the landscape or servicing layout is fixed. The project team should understand which nearby rooms, spaces and other equipment the assessor needs to consider. Also make uncertainty visible on the plan.

If a screen or enclosure is proposed, ask the acoustic and building-services designers to review the same detail. A measure that changes airflow or access needs coordinated review. Then record how the installer will deliver the accepted design.

Illustrative example: a unit moves from a side passage to a courtyard after the calculation. Send the revised layout and equipment information back for review. Do not carry the earlier conclusion into the application simply because the model number has stayed the same.

Make the assessment useful at installation and handover

Finally, keep the accepted equipment, drawing revision and operational assumptions with the installation brief. Also name the person who will refer substitutions back to the assessor. Then check that the final information describes what the contractor will install.

Our plant acoustic assessment briefing guide explains the wider information handover. To discuss an uncertain route or evidence gap, send ACP the site, proposal and available equipment information.

For an existing heat-pump noise concern

An investigation of installed equipment is a different brief from a pre-installation calculation. Record when the sound occurs, where it is heard, the equipment settings and any changes since installation. Share existing reports and commissioning records with the appointed specialist. The investigation should establish the actual circumstances before proposing a remedy.

Questions about heat-pump noise at night

Is there one universal night-time limit for every heat pump?

No. Identify the jurisdiction, planning route, assessment method and any site-specific requirements. A method’s criterion at a defined position should not be presented as a universal boundary limit.

Can we use the quiet-mode number from a brochure?

Only where the applicable method permits the input and its conditions are justified. MCS 020 a) Issue 1.1 does not allow low-noise-mode sound power as its specified calculation input.

Will switching a heat pump off at night solve the assessment?

Do not assume that it will. The heating designer must consider system performance, while the acoustician checks whether the operating restriction is appropriate for the assessment route.

Does passing a calculation resolve every possible complaint?

No. A calculation answers its defined question using stated assumptions. Installation defects, altered settings or a different context may need separate investigation. Keep a clear installation and commissioning record.

What information should we send ACP?

Send the location, proposed unit and data sheets, scaled plans, neighbouring windows, intended operation and the planning question. Include any existing assessment and explain what has changed.

References and scope

  1. IOA and CIEH: Domestic Air Source Heat Pumps — Professional Advice Note (2026)Official publication page and context for proportionate assessment outside permitted development.
  2. IOA and CIEH: full 2026 advice note, including annexFour-page primary document. Pages 1–2 set out the assessment routes, receiver criterion and sound-power selection. The note is professional advice, not a new permission or UK-wide permitted-development rule.
  3. MCS: MCS 020 a), Issue 1.1, 14 April 2025Air Source Heat Pump Sound Calculation for permitted-development installations. Step 3 specifies sound-power inputs and excludes low-noise-mode sound power.

Sources checked 29 October 2026. This guide supports project coordination in England; apply the current documents and specialist advice for your scheme.